Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

Technical provisions relating to waste incineration plants and waste co-incineration plants PART 1 Definitions For the purpose of this Annex the following definitions shall apply:
(a) ‘existing waste incineration plant’ means one of the following waste incineration plants:
(i) which was in operation and had a permit in accordance with applicable Union law before 28 December 2002, (ii) which was authorised or registered for waste incineration and had a permit granted before 28 December 2002 in accordance with applicable Union law, provided that the plant was put into operation no later than 28 December 2003, (iii) which, in the view of the competent authority, was the subject of a full request for authorisation before 28 December 2002, provided that the plant was put into operation not later than 28 December 2004;
(b) ‘new waste incineration plant’ means any waste incineration plant not covered by point (a). PART 2 Equivalence factors for dibenzo-p-dioxins and dibenzofurans
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

For the determination of the total concentration of dioxins and furans, the mass concentrations of the following dibenzo-p-dioxins and dibenzofurans shall be multiplied by the following equivalence factors before summing: PART 3 Air emission limit values for waste incineration plants
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

1. All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases. They are standardised at 11 % oxygen in waste gas except in case of incineration of mineral waste oil as defined in point 3 of Article 3 of Directive 2008/98/EC, when they are standardised at 3 % oxygen, and in the cases referred to in Point 2.7 of Part 6.
1.1. Daily average emission limit values for the following polluting substances (mg/Nm3) 1.2. Half-hourly average emission limit values for the following polluting substances (mg/Nm3) 1.3. Average emission limit values (mg/Nm3) for the following heavy metals over a sampling period of a minimum of 30 minutes and a maximum of 8 hours These average values cover also the gaseous and the vapour forms of the relevant heavy metal emissions as well as their compounds.
1.4. Average emission limit value (ng/Nm3) for dioxins and furans over a sampling period of a minimum of 6 hours and a maximum of 8 hours. The emission limit value refers to the total concentration of dioxins and furans calculated in accordance with Part 2.
1.5. Emission limit values (mg/Nm3) for carbon monoxide (CO) in the waste gases:
(a) 50 as daily average value;
(b) 100 as half-hourly average value;
(c) 150 as 10-minute average value. The competent authority may authorise exemptions from the emission limit values set out in this point for waste incineration plants using fluidised bed technology, provided that the permit sets an emission limit value for carbon monoxide (CO) of not more than 100 mg/Nm3 as an hourly average value.
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

2. Emission limit values applicable in the circumstances described in Article 46(6) and Article 47. The total dust concentration in the emissions into the air of a waste incineration plant shall under no circumstances exceed 150 mg/Nm3 expressed as a half-hourly average. The air emission limit values for TOC and CO set out in points 1.2 and 1.5(b) shall not be exceeded.
3. Member States may lay down rules governing the exemptions provided for in this Part. PART 4 Determination of air emission limit values for the co-incineration of waste
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

1. The following formula (mixing rule) shall be applied whenever a specific total emission limit value ‘C’ has not been set out in a table in this Part. The emission limit value for each relevant polluting substance and CO in the waste gas resulting from the co-incineration of waste shall be calculated as follows: Vwaste : waste gas volume resulting from the incineration of waste only determined from the waste with the lowest calorific value specified in the permit and standardised at the conditions given by this Directive. If the resulting heat release from the incineration of hazardous waste amounts to less than 10 % of the total heat released in the plant, Vwaste must be calculated from a (notional) quantity of waste that, being incinerated, would equal 10 % heat release, the total heat release being fixed. Cwaste : emission limit values for waste incineration plants set out in Part 3 Vproc : waste gas volume resulting from the plant process including the combustion of the authorised fuels normally used in the plant (wastes excluded) determined on the basis of oxygen contents at which the emissions must be standardised as set out in Union or national law. In the absence of legislation for this kind of plant, the real oxygen content in the waste gas without being thinned by addition of air unnecessary for the process must be used. Cproc : emission limit values as set out in this Part for certain industrial activities or in case of the absence of such values, emission limit values of plants which comply with the national laws, regulations and administrative provisions for such plants while burning the normally authorised fuels (wastes excluded). In the absence of these measures the emission limit values set out in the permit are used. In the absence of such permit values the real mass concentrations are used. C : total emission limit values at an oxygen content as set out in this Part for certain industrial activities and certain polluting substances or, in case of the absence of such values, total emission limit values replacing the emission limit values as set out in specific Annexes of this Directive. The total oxygen content to replace the oxygen content for the standardisation is calculated on the basis of the content above respecting the partial volumes. All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases. Member States may lay down rules governing the exemptions provided for in this Part.
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

2. Special provisions for cement kilns co-incinerating waste 2.1. The emission limit values set out in points 2.2 and 2.3 apply as daily average values for total dust, HCl, HF, NOx, SO2 and TOC (for continuous measurements), as average values over the sampling period of a minimum of 30 minutes and a maximum of 8 hours for heavy metals and as average values over the sampling period of a minimum of 6 hours and a maximum of 8 hours for dioxins and furans. All values are standardised at 10 % oxygen. Half-hourly average values shall only be needed in view of calculating the daily average values.
2.2. C – total emission limit values (mg/Nm3 except for dioxins and furans) for the following –polluting substances 2.3. C – total emission limit values (mg/Nm3) for SO2 and TOC The competent authority may grant derogations for emission limit values set out in this point in cases where TOC and SO2 do not result from the co-incineration of waste.
2.4. C- total emission limit values for CO The competent authority may set emission limit values for CO.
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

3. Special provisions for combustion plants co-incinerating waste 3.1. Cproc expressed as daily average values (mg/Nm3) valid until the date set out in Article 82(5) For determining the total rated thermal input of the combustion plants, the aggregation rules as defined in Article 29 shall apply. Half-hourly average values shall only be needed in view of calculating the daily average values. Cproc for solid fuels with the exception of biomass (O2 content 6 %): Cproc for biomass (O2 content 6 %): Cproc for liquid fuels (O2 content 3 %): 3.2. Cproc expressed as daily average values (mg/Nm3) valid from the date set out in Article 82(6) For determining the total rated thermal input of the combustion plants, the aggregation rules as defined in Article 29 shall apply. Half-hourly average values shall only be needed in view of calculating the daily average values.
3.2.1. Cproc for combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines Cproc for solid fuels with the exception of biomass (O2 content 6 %): Cproc for biomass (O2 content 6 %): Cproc for liquid fuels (O2 content 3 %): 3.2.2. Cproc for combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines Cproc for solid fuels with the exception of biomass (O2 content 6 %): Cproc for biomass (O2 content 6 %): Cproc for liquid fuels (O2 content 3 %): 3.3. C — total emission limit values for heavy metals (mg/Nm3) expressed as average values over the sampling period of a minimum of 30 minutes and a maximum of 8 hours (O2 content 6 % for solid fuels and 3 % for liquid fuels) 3.4. C — total emission limit value (ng/Nm3) for dioxins and furans expressed as average value measured over the sampling period of a minimum of 6 hours and a maximum of 8 hours (O2 content 6 % for solid fuels and 3 % for liquid fuels)
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

4. Special provisions for waste co-incineration plants in industrial sectors not covered under Points 2 and 3 of this Part 4.1. C — total emission limit value (ng/Nm3) for dioxins and furans expressed as average value measured over the sampling period of a minimum of 6 hours and a maximum of 8 hours: 4.2. C – total emission limit values (mg/Nm3) for heavy metals expressed as average values over the sampling period of a minimum of 30 minutes and a maximum of 8 hours: PART 5 Emission limit values for discharges of waste water from the cleaning of waste gases PART 6 Monitoring of emissions 1. Measurement techniques 1.1. Measurements for the determination of concentrations of air and water polluting substances shall be carried out representatively.
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

1.2. Sampling and analysis of all polluting substances including dioxins and furans, as well as the quality assurance of automated measuring systems and the reference measurement methods to calibrate them, shall be carried out in accordance with CEN-standards. If CEN standards are not available, ISO, national or other international standards which ensure the provision of data of an equivalent scientific quality shall apply. This applies also to the quality assurance system of the laboratory performing the sampling and analysis. Automated measuring systems shall be subject to control by means of parallel measurements with the reference methods at least once per year.
1.3. At the daily emission limit value level, the values of the 95 % confidence intervals of a single measured result shall not exceed the following percentages of the emission limit values: Periodic measurements of the emissions into air and water shall be carried out in accordance with points 1.1 and 1.2.
2. Measurements relating to air polluting substances
Directive 2010/75/EU of the European Parliament and of the Council of 24 November 2010 on industrial emissions (integrated pollution prevention and control) (recast) (Text with EEA relevance)

article  annex_VI

CELEX:  02010L0075-20240804

2.1. The following measurements relating to air polluting substances shall be carried out:
(a) continuous measurements of the following substances: NOx, provided that emission limit values are set, CO, total dust, TOC, HCl, HF, SO2;
(b) continuous measurements of the following process operation parameters: temperature near the inner wall or at another representative point of the combustion chamber as authorised by the competent authority, concentration of oxygen, pressure, temperature and water vapour content of the waste gas;
(c) at least two measurements per year of heavy metals and dioxins and furans; one measurement at least every 3 months shall, however, be carried out for the first 12 months of operation.
2.2. The residence time as well as the minimum temperature and the oxygen content of the waste gases shall be subject to appropriate verification, at least once when the waste incineration plant or waste co-incineration plant is brought into service and under the most unfavourable operating conditions anticipated.